DA2-B0-34-615-121-C [Carling Technologies]
Circuit Breakers 15 A TWO POLE;型号: | DA2-B0-34-615-121-C |
厂家: | Carling Technologies |
描述: | Circuit Breakers 15 A TWO POLE 电路保护 |
文件: | 总8页 (文件大小:1579K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
D-Series
Circuit Breaker
Designed for snap-on-back panel rail mounting on either
a 35mm x 7.5mm, or a 35mm x 15mm Symmetrical Din
Rail, allowing rapid and simple mounting and removal
of the breaker. It features recessed, wire-ready, touch-
proof, shock-resistant terminals, suitable for automatic
screwdriver assembly, as well as “Dead Front”construction
characteristics.
Available with a Visi-Rocker two-color actuator, which
can be specified to indicate either the ON or the TRIPPED/
OFF mode, or solid color rocker or handle type actuators.
All actuator types fit in the same industry standard panel
cutouts.
Features:
0.02 - 50 Amps
480 VAC or 65 VDC
1-4 poles (Handle)
1-3 poles (Rocker)
Choice of Time Delays
DIN rail mounting
Precise temperature independent operation
Wiping contacts – mechanical linkage with two-step
Finger safe terminals
Common trip linkage between poles – ensures that an
overload in one pole will trip all adjacent poles
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
|
2
D-Series Circuit Breaker - General Specifications
Mechanical
Electrical
Maximum Voltage
AC, 480 wye/277 VAC
(See Table A), 50/60 Hz, 65VDC
Endurance
10,000 ON-OFF operations @ 6
per minute; with rated Current
and Voltage.
All D-Series Circuit Breakers will
trip on overload, even when
actuator is forcibly held in the ON
position.
Standard Current Coils 0.100, 0.250, 0.500, 0.750, 1.00,
2.50, 5.00, 7.50, 10.0, 15.0, 20.0,
25.0, 30.0, 35.0, 40.0 & 50.0.
Trip Free
Other ratings available -
consult factory.
Standard Voltage Coils DC - 6V, 12V; AC - 120V, other
ratings available, see ordering
scheme.
Trip Indication
The operating actuator moves
positively to the OFF position
when an overload causes the
breaker to trip.
Insulation Resistance
Minimum of 100 Megohms at 500
VDC.
Physical
Number of Poles
Dielectric Strength
UL, CSA: 1960 V 50/60 Hz for one
minute between all electrically
isolated terminals. D-Series circuit
breakers comply with the 8mm
spacing and 3750V 50/60 Hz
dielectric requirements from
hazardous voltage to operator
accessible surfaces and between
adjacent poles per Publications
EN 60950 and VDE 0805.
Rocker Type: 1-3; Handle Type:
1-4
Internal Circuit Config. Switch Only and Series Trip with
current or voltage trip coils.
Weight
Approximately 128 grams/pole
(Approximately 4.57 ounces/pole)
Housing - Black; Actuator - See
Ordering Scheme.
Mounts on a standard 35mm
Symmetrical DIN Rail (35 x 7.5 or
35 x 15mm per DIN EN5002).
Standard Colors
Mounting
Resistance, Impedance Values from Line to Load Terminal
- based on Series Trip Circuit
Breaker
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Environmental
Designed and tested in accordance with requirements of
specification MIL-PRF-55629 & MIL-STD-202 as follows:
Shock
Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short
curves tested @ 90% of rated
current.
Vibration
Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz,
at rated current per Method 204C,
Test Condition A. Instantaneous
and ultra-short curves tested at
90% of rated current.
Moisture Resistance
Method 106D, i.e., ten 24-hour
cycles @ + 25°C to +65°C, 80-
98% RH.
Pulse Tolerance Curves
Salt Spray
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Thermal Shock
Operating Temperature -40° C to +85° C
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
D-Series Circuit Breaker - General Specifications
3
Electrical Tables
Table A: Lists UL Recognized, CSA Accepted and VDE Certified configurations and performance capabilities as a
Component Supplementary Protector.
Table A Notes:
1
2
DC and 1Phase 277 V ratings are 1 or 2 poles breaking. Three phase ratings are 3 poles breaking.
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full
load amps not to exceed 150 A for 250V rating and 125 A for 277 and 480 V ratings.
UL recognition and CSAAcceptance at 480 volts refers to 3 and 4 pole versions, used only in a 3 phase WYE connected
circuit or 2 pole versions connected with 2 poles breaking 1 phase and backed up with series fusing per note 2
3
Agency Certifications
Component Supplementary
Protector under Class 3215 30,
File 047848 0 000
UL Recognized
CSA Accepted
Component Recognition Program
UL Standard 1077
as Protectors, Supplementary
(Guide QVNU2, File E75596)
CSA Standard C22.2 No. 235
EN60934, VDE 0642 under File
No. 10537
UL Listed
UL Standard 508
VDE Certified
Switches, Industrial Control
(Guide NRNT2, File E148683)
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
4
D-Series Handle & Rocker – Ordering Scheme
D A 3 B0
450 1 2 1 C
10
8
9
10
Agency
Approval
1
2
3
4
5
6
7
Actuator
Color
Mounting/
Voltage
Series
Actuator
Poles
Circuit
Frequency
& Delay
Current Rating
Terminal
1 SERIES
D
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
050 0.050
075 0.075
080 0.080
085 0.085
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
410 1.000
512 1.250
413 1.300
414 1.400
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
532 3.250
435 3.500
436 3.600
440 4.000
445 4.500
547 4.750
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
572 7.250
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
619 19.000
620 20.000
621 21.000
622 22.000
623 23.000
624 24.000
625 25.000
626 26.000
627 27.000
628 28.000
629 29.000
630 30.000
632 32.000
635 35.000
640 40.000
645 45.000
650 50.000
2 ACTUATOR1
Handle2
A
B
Handle, one per pole
Handle, one per multipole unit
Visi-Rocker3
C
D
E
F
G
H
Indicate ON, vertical legend
Indicate ON, horizontal legend
Indicate ON, no legend (VDE approval not available with no legend)
Indicate OFF, vertical legend
Indicate OFF, horizontal legend
Indicate OFF, no legend (VDE approval not available with no legend)
Single Color Rocker3
J
K
L
Vertical legend
Horizontal legend
No legend (VDE approval not available with no legend)
OR VOLTAGE COIL (VOLTS, MIN. TRIP RATING)5
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
J06 6 AC, 5 AC
J12 12 AC, 10 AC
J18 18 AC, 15 AC
J24 24 AC, 20 AC
J48 48 AC, 40 AC
K20 120 AC, 65 AC
L40 240 AC, 130 AC
7 TERMINAL
1
2
#10 Screw & Pressure Plate for Direct Wire Connection
#10 Screw without Pressure Plate
3 POLES
1
2
3
4
One
Two
Three
Four
8 ACTUATOR COLOR & LEGEND
Actuator or
Visi-Color Marking:
Marking Color:
Single Color
4 CIRCUIT
Visi-Rocker
A0
B0
C0
Switch Only (No Coil)4
Series Trip (Current)
Series Trip (Voltage)
Color
White
Black
Red
I-O ON-OFF Dual
Rocker/Handle (Actuator Black)7
A
C
F
B
D
G
J
1
2
3
4
5
6
7
8
Black
White
White
White
White
Black
Black
Black
White
N/A
Red
Green
Blue
H
K
M
P
R
Green
Blue
5 FREQUENCY & DELAY
L
03
105
11
12
14
16
205
21
22
24
DC 50/60Hz, Switch Only
DC Instantaneous
DC Ultra Short
DC Short
DC Medium
26
32
34
36
50/60Hz Long
DC, 50/60Hz Short
DC, 50/60Hz Medium
DC, 50/60Hz Long
50/60Hz Short, Hi-Inrush
50/60Hz Medium, Hi-Inrush
50/60Hz Long, Hi-Inrush
DC, Short, Hi-Inrush
DC, Medium, Hi-Inrush
DC, Long, Hi-Inrush
Yellow
Gray
Orange
N
Q
S
Yellow
Gray
Orange
426
446
466
526
546
566
DC Long
9 MOUNTING/VOLTAGE
MOUNTING STYLE
Threaded Insert
50/60Hz Instantaneous
50/60Hz Ultra Short
50/60Hz Short
VOLTAGE
1
6-32 x 0.195 inches
6-32 X 0.195 inches
ISO M3 x 5mm
< 300
≥ 300
< 300
≥ 300
50/60Hz Medium
C8
2
D8
ISO M3 x 5mm
Notes:
1
2
Handle breakers available up to four poles. Rocker breakers available up to three poles.
Actuator Code:
A: Multi-pole units factory assembled with common handle tie.
B: Handle location as viewed from front of breaker:
2 pole - left pole
10 AGENCY APPROVAL
C
UL Recognized & CSA Accepted
VDE Certified, UL Recognized & CSA Accepted
D9
3 pole - center pole
4 pole - two handles at center poles
Multipole rocker breakers have one rocker per breaker, as viewed from the front of the
panel. Two pole - left pole. Three pole - center pole
≤ 30A, select Current Rating code 630. 31-50A, select Current Rating code 650.
Voltage coil only available with delay codes 10 & 20.
Available to 50A max with circuit code BO only.
Color shown is visi and legend with remainder of rocker black.
≥ 300V: Three pole breaker 3Ø or 2 pole breaker 1Ø, UL/CSA limited to 30 FLA max.
VDE Approval requires Dual (I-O, ON-OFF) or I-O markings
3
4
5
6
7
8
9
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
D-Series – Circuit & Terminal Diagram
5
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
6
D-Series Rocker – Form & Fit Drawings
Notes:
1
2
3
4
All dimensions are in inches [millimeters].
Tolerance ±.020 [.51] unless otherwise specified.
Dimensions apply to all variations shown. Notice that circuit breaker line and load terminal orientation on indicate OFF is opposite of indicate ON.
For pole orientation with horizontal legend, rotate front view clockwise 90°.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
|
D-Series – Form & Fit Drawings
7
Notes:
1
2
All dimensions are in inches [millimeters].
Tolerance ±.010 [.25] unless otherwise specified.
60 Johnson Avenue • Plainville, CT 06062 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
East Region Sales Office, CT • ersm@carlingtech.com
Midwest Region Sales Office, IL • mrsm@carlingtech.com
West Region Sales Office, CA • wrsm@carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacific Ltd.,
Kowloon, Hong Kong
Int + 852-2737-2277 • Fax: Int + 852-2736-9332
Email: sales@carlingtech.com.hk
Shenzhen, China • shenzhen@carlingtech.com
Shanghai, China • shanghai@carlingtech.com
Pune, India • india@carlingtech.com
Kaohsiung, Taiwan • taiwan@carlingtech.com
Yokohama, Japan • japan@carlingtech.com
Europe/Middle East/Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Int + 44 1392-364422 • Fax: Int + 44 1392-364477
Email: ltd.sales@carlingtech.com
GmbH, Germany • gmbh@carlingtech.com
SAS, France • sas@carlingtech.com
REV_CB_D_01_2014
相关型号: